TS790 & TS900
Intruder Alarm Control Panels
Installation & Programming
Manual
_
~
Engineers menu 2
Select option :-
_
~
OPEN
_
~
Engineers menu 2
Select option :-
_
~
_
~
OPEN
1A
D
C
B
23
7
6
5
4
89
0
ENT
ESC
_
~
SYSTEM OPEN
17: 30 Wed 11 NOV
SIL EN TZONE OMIT
CHIMENEW COD E 24 Hr OMI T
WALKTESTBELLTESTPar t Se t
Par t Se t
Part Se t
RE SET
1
A
B
C
D
23
456
7
ENT ESC
8
0
9
Sett ing th e Sys t em
Enter your pa sscode XXXX
then leave the protected area.
Unsetting the System
Go directly to the keypad and
en ter y our p assc ode XXXX.
Resetting
Enter your pa sscode XXXX followed
by EN T the n 3. Telephon e you r alarm
com pan y a nd fol low thei r ins truct ions.
!
See User Manual
FULL SET
Zobrazit stránku 0
1 2 3 4 5 6 ... 67 68

Shrnutí obsahu

Strany 1 - TS790 & TS900

TS790 & TS900Intruder Alarm Control PanelsInstallation & ProgrammingManual_~Engineers menu 2Select option :-_~OPEN_~Engineers menu 2Select opt

Strany 2

Control Panel PCB Layout6System Installation TS790 & TS900 Installation ManualOUTPUT MODULE PRINTER1AMPNODE SUPPLYREMOTEKEYPADJP3DIGI-MODEMFACTORY

Strany 3 - Engineer's Menu 2

Connection Terminals & IndicatorsThe main PCB has the following “Jumper Plugs” (JP)and indicator LEDS:JP1 PRINTERThis 6-pin plug is used for conne

Strany 4 - Appendices

Mains ConnectionThe mains supply is connected to a 3 way "EuroType" fused terminal block, which is fitted with a315mA fuse. All electrical c

Strany 5 - Control Panel

 Tamper Switch.Remote Keypad case tamper ENT Key Disable.If the “ENT” key is enabled the remote keypad canbe used to set/unset and access all user m

Strany 6 - Specifications

When the link is set to the enabled position thesounder is only enabled when the remotekeypad programmable output is active. Forexample, to make the k

Strany 7 - Cable Routing

TS900 Node Layout11TS790 & TS900 Installation Manual System InstallationABFG ABFGAUX 12VAUX 12V500mANODE I/DJP2ZAZHZGZFZEZCZDZBCIRCUIT ACIRCUIT HC

Strany 8 - Remote Network Wiring

TS700 LEC InstallationThe TS700 LEC (Local Expansion Card) isconnected to the “Remote Network” and providestwo additional programmable detection circu

Strany 9 - Control Panel Installation

End Of LineThe EOL method requires the following:lThe detector alarm contacts must have a 4K7shunt resistor fitted.lA 2K2 End of Line (EOL) resistor m

Strany 10 - Control Panel PCB Layout

Installing an External Sounder from a NodeThe TS900 Node has two programmable outputs,these can be utilised to drive an external sounder.However, it i

Strany 11

Digicom/RedCARE InstallationA stand alone digital communicator, RedCARESTU or Paknet interface card can be connected tothe control panel using the fol

Strany 13 -  ENT Key Disable

Output Modules Installation (CPA6.OM)Output Modules (CPA6.OM) can be used toprovide a set of outputs to LEDs or relays to indicateeither circuit alarm

Strany 14 - Engineer’s Keypad

Programmable OutputsThe TS790/900 has many programmable outputswhich can be used to drive relays, LED’s etc. Eachoutput can be programmed for a differ

Strany 15 - Figure 11. TS900 Node Layout

Installing a Monitored Power SupplyThe TS790/TS900 can be configured to monitor the519XB power supply unit using the 519FM faultmonitor PCB. The 519FM

Strany 16 - Wiring Detection Circuits

Power-Up ChecksWhen the initial power-up checks have beencompleted, check the following:1. Switch off the 240V mains supply and measurethe DC voltage

Strany 17 - External Sounder Connections

Section Option DefaultCircuitsCircuit 07 Exit TerminatorCircuit 08 PA AudibleCircuit 09 Final ExitCircuit 10 PA AudibleCircuit 11 - 56 Not UsedSystem

Strany 18 - Extension Loudspeakers

Engineer’s Menu 1IntroductionEngineers menu 1 is the first of three engineersmenus, which is selected when the engineer’spasscode is entered. The engi

Strany 19 - Plug-on Digicom Installation

Panel OutputsOutputs 1-4onthecontrol panel and remotekeypad outputs 5 - 8 can be programmed to anyof the output types shown on page .22Digicom Output

Strany 20 - Connecting a Printer

No/Type Description006P.A.Activates when a PA alarm is detectedand deactivates when the alarm isreset.007FireActivates when a Fire alarm isdetected an

Strany 21 - Programmable Outputs

No/Type Description041Time Switch BThis output is controlled by the settings of“Time Switch B” (see Engineers Menu 3)042Time Switch CThis output is co

Strany 22 - Initial Power-Up

Program CircuitsThe TS790 can monitor up to 16 detection circuits,whereas the TS900 can monitor up to 56 detectioncircuits. Each circuit must be progr

Strany 23 - NVM Defaults

ContentsOverviewIntroduction . . . . . . . . . . . . . . . . . . . . . . . . . 1System Architecture . . . . . . . . . . . . . . . . . . . 1Control Pan

Strany 24

Circuit AttributesEach circuit type can have one or more attributesassigned to it to alter its operation. The followingcircuit attributes can be progr

Strany 25 - Introduction

System TimersThe system timers are as follows:00 Test Call AtThis timer controls the hour at which the controlunit sends a timed test call. For exampl

Strany 26 - Programmable Output Types

07 Bell DelayThis timer delays the activation of the externalbell/sounder and internal sounders. This timerhas a working range of 000-199 minutes. Not

Strany 27

18 Ward Menu DurationIf the timer is set to 000 the “Code Set Group”passcodes function as normal, i.e., when theuser enters their passcode the exit ti

Strany 28

Setting ModesThe setting mode for full set and each part set canbe configured to the following setting modes:1 Final ExitThe system will set when the

Strany 29 - Program Circuits

Remote Reset AlgorithmWhen the system is programmed for “EngineerReset” the requirement to send an engineer to sitecan be overridden by the user by us

Strany 30 - Circuit Attributes

10 O/M's Mimic CircuitsWhen programmed as “Yes" the outputmodules mimic circuit activations. Whenprogrammed as ”No" output modules give

Strany 31 - System Timers

Goto User Menu 1This option allows the engineer to access “Usermenu 1", the flowchart below shows the optionswithin ”User menu 1", for full

Strany 32

View Location Text (LCD Only)This option allows the engineer to view the panellocation text. The text message is programmed in"Engineers menu 3&q

Strany 33

Engineer's Menu 2IntroductionEngineer's menu 2 is selected by pressing the [ENT]key whilst Engineer's menu 1 is selected. Eachmenu opti

Strany 34 - Do System Print

Menu Contents. . . . . . . . . . . . . . . . . . . . . 35View Circuits . . . . . . . . . . . . . . . . . . . . . . . . . 36Set System Time . . . . . .

Strany 35 - Configuration

View CircuitsEach detection circuit may be viewed toascertain its status. The circuit status conditionsand resistance are shown below:Status Response

Strany 36

Chime CircuitsThis option allows an alternative method ofprogramming circuits as “chime”.Alter 24Hr GroupCircuit types “24hr” and “Auxiliary” with the

Strany 37 - Goto User Menu 1

Log Event CodesView System LogThe engineer can use this option to view thesystem log. The [A] and [C] keys allow you to scrollbackwards and forwards t

Strany 38 - Relearn Hardware

Log Event Codes39TS790 & TS900 Installation Manual Engineer's Menu 2LCD Starburst LED DescriptionDATE CHANGEDDATE CHGDcSystem Date changed.DE

Strany 39

Log Event CodesReset User Code 1This option allows the installation engineer to resetthe master user (user 01) back to the factorydefault code of “567

Strany 40 - Change Passcode

Engineers Menu 3IntroductionEngineers menu 3 is selected by pressing the [ENT]whilst Engineers menu 2 is selected. Each menuoption can be selected by

Strany 41 - Configure Wards

Time SwitchesThe TS790/TS900 has three programmable timeswitches. Each time switch can be programmedwith up to three separate on/off times and madeto

Strany 42 - View System Log

Part Set GroupsThis option allows the engineer to define how thethree part set buttons operate. Each group can beprogrammed so that it sets any combin

Strany 43

Engineers Name (LCD Only)This option allows the engineer to assign a name (7characters) to user 00. When using the view logoption you can press the [B

Strany 44 - StarburstLCD

Location TextThis option allows the engineer to program a 32character location message. When “Engineersmenu 1" is selected the engineer can view

Strany 45 - Menu Contents

OverviewIntroductionThe TS790 and TS900 alarm control systems havebeen designed to suit medium to large installationsites. The TS900 system can be exp

Strany 46 - Time Switches Flowchart

VoltageWhen this test option is selected the batterycharging voltage at the control panel is displayed,the accuracy of this measurement is ± 0.2V.View

Strany 47 - Code Set Group Operation

Custom Outputs A & BThese options allows the engineer to programboth custom outputs. The diagram belowrepresents the logic circuit for the custom

Strany 48 - Banner Message

Modem Options (LCD Only)This option allows the engineer to access thefollowing modem options:Call Back No.1This option allows the first call back tele

Strany 49 - Current Consumption

49TS790 & TS900 Installation Manual Engineers Menu 3Digi programmingPress ESC to end6ENTENTENTENTENTENTENTENTENTENTENTENTModem optionsSelect Optio

Strany 50 - View Inactive Circuits

Reset DigicomWhen the system is powered up, the control panellogs-on the device that is connected to thedigicom plug (JP3). If the device is changed o

Strany 51 - Custom Outputs A & B

AppendicesPoint ID Extended ReportingPoint ID extended reporting is a new format whichwhen used with the DC58 or DC58M can be usedto report circuit ID

Strany 52 - Modem Options (LCD Only)

52Appendices TS790 & TS900 Installation ManualPPPPPRKCCCCCCSSCPCPRKKey:10987621354Bedroom 1Bedroom 2BathroomLandingBedroom 3LoungeGarageKitchenDin

Strany 53 - Program Digi Flowchart

Domestic Part-Set Application ExampleThe TS790/900 is very flexible in the way that thesystem can be part-set. The system may bepart-set by using the

Strany 54 - Reset Digicom

Defining Part-Set buttons to Arm a Ward(s)This method of defining the part set groupsrequires you to think of the system in terms ofseparate areas of

Strany 55 - Point ID Extended Reporting

55TS790 & TS900 Installation Manual AppendicesPPPPPPPPPPCCCCCCCCCCRKCPRKRKRKRKCPKey:12143576891011121315164Workshop CanteenStoresSalesOfficeServic

Strany 56

Remote KeypadsUp to 4 remote keypads can be connected to thecontrol panel. Each remote keypad has twodetection circuits and a single switched -veoutpu

Strany 57

Commercial Part-Set ApplicationThis application example shows how to use the"Code Set Groups" to set and unset different areaswithin a comme

Strany 58

1. Program the Detection Circuit as a “Key Point”and set the attributes as “F***|*A**”.The“F”attribute indicates that the “Full Set Group” isselected

Strany 59 - Service Department

1. If a plug-on digicom is being used programthe digicom channels as shown below, see“Plug-on Digi Channels”, on page 22. If astand-alone digicom is b

Strany 60 - Key Point Application Example

Setup New UsersThe TS790/TS900 allows up to 31 users to operatethe alarm system, each user is assigned a usertype and a passcode. User 01 is the maste

Strany 61

Code Set Group BUsers 02-31 can be programmed as "Code SetGroup B". This user type only allows the wardsassigned by the installation company

Strany 62 - Text Editing Keys

Quick Reference Engineers MenusEngineers Menu 1key Options Page1Program Panel Outputs1 = Panel Output 1 (relay)2 = Panel Output 2 (-ve)3 = Panel Outpu

Strany 63 - Setup New Users

Quick Reference Engineers MenusEngineers Menu 2key Options Page1View CircuitsA = Scroll Next CircuitC = Scroll Previous Circuit362Set System TimeEnter

Strany 64 - Setup New Users Flowchart

Quick Reference Engineers MenusProgrammable Output TypesNo. Output Type000 Bell On001 Strobe On002 Switch 12V003 Detector Reset004 Walk Test005 Alarm

Strany 65

496487 Issue 3Cooper Security Ltd.Security House, Xerox Business Park,Mitcheldean, Gloucestershire,GL17 0SZ. EnglandProduct Support Tel: +44 (0)1594 5

Strany 66

System InstallationCable RoutingWhen installing cables, the following should benoted:Screened cable may prove necessary if theNetwork is run adjacent

Strany 67

Remote Network WiringDevices on the “Remote Network” require a 6 corecable for interconnection, and may beconnected in a “star” or “daisy-chain”config

Strany 68 - 496487 Issue 3

Control Panel InstallationProceed as follows:1. Open the control panel by removing the threescrews from the front cover. Remove the coverby sliding it